VFD. XSY AT4 220v 1phase to 380v 3phase advice sort

Advert

VFD. XSY AT4 220v 1phase to 380v 3phase advice sort

Home Forums General Questions VFD. XSY AT4 220v 1phase to 380v 3phase advice sort

Viewing 25 posts - 1 through 25 (of 74 total)
  • Author
    Posts
  • #474211
    Andrew Firman
    Participant
      @andrewfirman12129

      I have a couple of 2.2Kw XSY AT4 which I want to use to power a couple of 380V 3 phase star wired motors using 220v single phase supply.

      I've bench run a 1/2hp motor successfully using the key panel for control but have run into a problem when trying to control speed using a 10K pot. For some reason I'm only able to obtain exactly half the max hz set in the vfd that I was able to achieve with the keyboard. I'm hoping someone will be able to advise why this might be the case and how I can get the full hz range using the Pot.

      Unlike the other ATs in the series the AT4

      1: has no earth terminal . I was planning to earth the cooling fins but measured 85v ac between the fins and supply earth. Is this to be expected? Should I earth it?

      3803980c-8691-414e-ae2c-a4f8db2a287d.jpeg

      2: has only 1 COM terminal on the control ports. The voltage between this COM and the 5v/10v terminal measures 5v Could this be causing the half max hz with the Pot?

      225c578a-2bf1-4a1e-b03f-a430fbf1d5a5.jpeg

      The manual that came with the vfds is the same AT series manual that other people have posted for the AT1 Thanks in anticipation.

      Advert
      #27388
      Andrew Firman
      Participant
        @andrewfirman12129
        #474227
        Clive Foster
        Participant
          @clivefoster55965

          Andrew

          I'd always understood that half speed running was normal if trying to run a star connected (400 v) motor off a 220 v inverter. As per this link **LINK** .

          Its possible that the internal parameter settings will allow the keypad to do things the control pot can't.

          I've encountered that before on another breed where the pot wouldn't run the motor up past 60 Hz yet the keypad would quite happily go much faster.

          Clive

          #474233
          Andrew Firman
          Participant
            @andrewfirman12129

            Clive,

            Thanks for response. I believe this vfd is supposed to be a “step up” vfd ie the output is 380v 3 phase at 50hz. I’ve used a true rms meter to confirm that this is in fact the case. The vfd is marketed as such too.

            I guess I could increase the max operating hz parameter to say 140hz. Then using the pot would give me a max hz of 70 hz.
            I wondered whether the two COM terminals on an AT1 are interconnected. The diagrams in the manual show the pot connected to one with all the other controls connected to the other one.

            Do you have any thoughts on the lack of protection earth and the measured 85v ac between supply earth and the cooling fins?

            #474236
            SillyOldDuffer
            Moderator
              @sillyoldduffer

              Had a look at the Manual and it says the voltage is 5/10V. And then silence – very unhelpful! It implies to me the reference voltage can be either 5V or 10V, therefore I'd expect a physical switch or parameter setting allowing it to be changed. And it sort of follows that a pot connected to 5V when VC1 expects up to 10V will only be able to run the motor up to half speed.

              Disaster : can't see a parameter setting in the manual, or any sign of a 5V / 10V switch on the VFD. Might be worth looking inside the case to see if there's a tiny slider switch on the board. Sorry if teaching granny to suck eggs but disconnect from the mains first and take extreme care not to touch anything metal inside because those big capacitors can store enough energy to deliver a hefty shock.

              Should be possible to prove whether or not it's lack of 10V causing the problem by substituting a 9V battery for the 5V terminal. (Connect – to COM and + to top of pot.) Wind the motor up gently from 0V on VC1 : if it keeps speeding up when the pot goes past half way, it strongly suggests 10V is needed. If the motor doesn't go faster beyond the pot's half way setting, don't push on regardless up to 9V in case it damages the input electronics.

              I don't know if its OK or not for the fins to be at 85V on an AT4. Probably OK because lots of power electronics are cooled that way. Heatsinks can be earthed or floating. The unit is meant to be operated inside a box, usually steel, and it's the user facing box that's earthed, not the VFD. If a unit doesn't come with an earth terminal, don't make one up!

              With luck an AT4 owner will be along who will explain all.

              Why is nothing ever easy?

              Dave

              #474238
              Anonymous

                The linked article has been discussed before; when I blew a rather large raspberry about it. After some discussion I think we decided that what he's actually doing is reducing the base speed of a star connected motor running from a 240V output inverter in order to maximise the constant power part of the curve. So I'd now blow half a raspberry.

                The speed of an induction motor is primarily determined by the applied frequency. Voltage doesn't come into it. For any given motor at a given frerquency the voltage will determine the phase currents which in turn determine the torque.

                I suspect the described problem is to do with internal parameters and/or the wiring of the pot not giving the voltages expected.

                On the VFD that I happen to have sitting on the bench the heatsink has screws in two corners and the case has two moulded earth symbols next to the screws. That implies that the semiconductors on the heatsink are electrically isolated from the heatsink and the heatsink can be earthed. That may not be the case for cheap VFDs. If there isn't a terminal somewhere explicitly marked as earth I'd immediately bury the unit in the earth and forget about it.

                Andrew

                #474257
                Andrew Firman
                Participant
                  @andrewfirman12129

                  Thanks Dave,

                  I have a steel enclosure which I’m going to mount the vfd in. I’m hoping Martin of Wick responds because I’m sure I read somewhere that he has an AT4.
                  As I have two of these I’ll check inside the one that has not been powered up. I’m not an electronics engineer so whether I’ll be able to identify what various components do is debatable. I do have a healthy respect for electricity and thankfully the large capacitors are very obvious though I’m sure it’s not just them that I should be wary of.

                  Thanks Andrew,

                  There is no earth symbol on the vfd that I can see The manual links the AT1 with the AT4 and there is conflict between text and diagrams asto whether there is a GND, I’ve seen YouTube videos in which an AT1 does have a marked earthing terminal adjacent to the N supply terminal. This terminal exists on my AT4 but there isn’t a screw in it and it is not marked as such implying nothing should be connected to the terminal. One definitely doesn’t get what one hasn’t paid for!!

                  Andrew F

                  #474275
                  SillyOldDuffer
                  Moderator
                    @sillyoldduffer

                    Posted by Andrew Firman on 23/05/2020 16:14:02:

                    As I have two of these I’ll check inside the one that has not been powered up. I’m not an electronics engineer so whether I’ll be able to identify what various components do is debatable.

                    Andrew F

                    Can you post photos of the insides? If there's a switch or jumper should be visible, but it may be tiny. I don't understand the 5V/10V thing at all. I've read worse manuals, maybe some clot just left a paragraph out when it went to the printers!

                    Dave

                    #474289
                    Andrew Firman
                    Participant
                      @andrewfirman12129

                      I’ve tried adding in 9v to the pot circuit and it doesn’t seem to alter the hz indicated on Vfd.
                      I can’t see any obvious jumpers or small switches on the board

                      719ec20f-e6d3-4a5a-9be6-94e3e3519747.jpeg

                      860ae65d-1cd9-4363-893b-903ae30d2c1e.jpeg

                      6501732e-109e-4e59-bc78-793df4cc8c93.jpeg

                      #474304
                      Andrew Firman
                      Participant
                        @andrewfirman12129

                        Dave, I was using a tarnished copper wire to do the 10v test so wasn’t getting more than 3v !!. Substituting an untarnished wire and Vfd indicated much higher hz and the motor ran at higher rpm than when using the 5v terminal on the Vfd. Problem now is how to change 5 to 10v.

                        Wondered whether Vfd is using current or voltage to alter hz?

                        If current then would a 5K pot instead of the10K pot I’ve been using solve the problem? Unfortunately I don’t have a 5K to use as a check.

                        Edited By Andrew Firman on 23/05/2020 19:20:20

                        #474322
                        SillyOldDuffer
                        Moderator
                          @sillyoldduffer

                          Looked at the photos and can't see anything resembling a switch! Pity now you've confirmed 10V will fix the problem!

                          It seems perverse that the manual says wire the pot to a voltage source that can't allow full speed. Something is missing!

                          The control is more likely to be voltage than current, but it will need some current. I don't think changing the pot will make any difference because too high a resistance would cause trouble at the low speed end not the high. However the manual says 4.7kohms rather than 10k. No harm in trying it, and it may be necessary – see next!

                          I think the answer is to drop the 24v terminal down to 10v with a resistor to give the pot more range. I'll do the sum and draw a circuit in another post. Watch this space!

                          Dave

                          #474331
                          SillyOldDuffer
                          Moderator
                            @sillyoldduffer

                            This should do the trick. A 6.8k ohm resistor between 24V and a 4.7k ohm potentiometer should put 9.8V onto the pot, close enough for government work.

                            speedpot24.jpg

                            Can't help thinking this shouldn't be necessary, but it should work until an AT4 expert explains!

                            I recommend going down to a 4k7 pot because it should avoid the current / voltage problem you mentioned.

                            Dave

                            #474347
                            Bruce Edney
                            Participant
                              @bruceedney59949

                              Apparently P73 and p74 are upper/lower analogue input values. Not in hz but some value derived from voltage in.

                              My friend has a couple of AT4 VFDs

                              #474359
                              James Walker
                              Participant
                                @jameswalker31828

                                Gents I have 2 of these VFDs commissioned on a Dah Lih mill. They run the Vertical, Horizontal and Power Feed motors. All motors are 380/400V 3ph. They are wired up to expect that range.

                                As noted this model VFD converts 220-240V 1PH in and spits out 380V/3PH.

                                The control pot I use is 10K. It is wired per the manuals instructions. I used Parameters P73 and P74 as noted by Bruce to adjust to get the response I wanted from the 10K pot.

                                I am happy to check and post the parameters I have set for all the key values if that is of interest and would be helpful.

                                I know when I did my install the level of info on this control as a bit like getting blood from a stone. So after lots of experimenting I solved most things and have it operating.

                                Cheers,

                                James.

                                #474371
                                Andrew Firman
                                Participant
                                  @andrewfirman12129

                                  Thanks David. I must admit I can’t find where it says to use a 4k7 pot in my manual but perhaps you are sizing it based on the stated supply 5v voltage and 20ma output plus Ohms law?

                                  That’s interesting Bruce, because the default (factory set) values I found on both my AT4s for p73 and P74 are almost exactly double those shown as the default values in the manual that came with the vfds. I’ll change them tomorrow and see whether the voltage increases from 5 to 10v. Fingers crossed!!
                                  I’d also be interested to know whether your friend noted any ac voltage between the cooling fins and supply earth.

                                  Edited By Andrew Firman on 23/05/2020 22:31:40

                                  #474373
                                  Martin of Wick
                                  Participant
                                    @martinofwick

                                    On my AT4 version, after some head scratching, I found the earth was located on the outer left-most terminal of the of the left hand green block above the 220v power input on your picture above- it is marked PE in minute lettering obscured by the casing (WTF!….yeah I know! …. don't start.), but don't take my word for it, check to ensure there is connection to the cooling plate.

                                    On my device, parameter 74 is 63500 and P75 is 4200 basically the span and offset values for the external control.

                                    Originally I noted these values along with other obscure parameters prior to use of the device (and a bloody good job too) seeing they were different from the 'manual'. As a test I input the values quoted in the 'manual' that were about half the 'as supplied' values and had similar half F issues.

                                    I then did a reset (bad mistake – don't ever be tempted to do one). The reset resulted in the same low values replaced in P74 and P75 (among a whole lot of other unwanted changes).

                                    I suggest you check what P74 P75 contain. If the stored values appear to be about 31000 and 1100, you could try the higher values quoted above and see if that helps and experiment from there until you are getting the range of control that you want.

                                    Above all take care, this thing is a pretty scary device to have floating around on the test bench.

                                     

                                     

                                    Edited By Martin of Wick on 23/05/2020 23:14:06

                                    #474375
                                    Martin of Wick
                                    Participant
                                      @martinofwick

                                      Hmmm….

                                      just seen your latest post… will be most interesting to see if reducing your P74 75 parameters to manual values actually gives you back full frequency control on the external input – It would then be the exact opposite of what happened in my case! Go figure!

                                      P67 is another parameter you may need to have regard to as it is often different from the one listed in the info sheet.

                                      I didn't detect any voltage between device and mains earth when I set up

                                      #474381
                                      James Walker
                                      Participant
                                        @jameswalker31828
                                        Posted by Martin of Wick on 23/05/2020 23:08:56:

                                        P67 is another parameter you may need to have regard to as it is often different from the one listed in the info sheet.

                                        Martin – did you determine what P67 does? It is marked as "Voltage coefficient" in the manual.

                                        #474466
                                        Andrew Firman
                                        Participant
                                          @andrewfirman12129

                                          Martin, thanks for advice, A couple of queries.

                                          Did your P 73 value also differ from manual? On my vfds supplied set at 61440 manual default 31440.

                                          P75 I need to double check, I’ve recorded a supplied setting of 5560 for one vfd and 1317 for the other. Manual default is 1130 .

                                          When you say no voltage difference between device and mains earth was that with the green PE terminal connected to mains earth?

                                          What is the measured voltage across 5v and COM terminals on your AT4?

                                          James, my P67 supplied setting is 45000. Manual default is 28500. – ostensibly a big difference.

                                          #474485
                                          Martin of Wick
                                          Participant
                                            @martinofwick

                                            Andrew,

                                            Some mistakes in my original post – I referred to P74 and P75, when I should have said P73 and P74.

                                            Originally out of the box, P73 was set at 61440 and P74 was set at 4096.

                                            And P75 was set at 4196 with P67 at 45000.

                                            I don't know what P75 and P67 do but have recorded the fact that they appear to change the reported output current and voltage on the VFD display.

                                            I checked and confirmed with a clamp on that changing P75 did also appear to change the output current very approximately inline with the observed variance in the VFD display. Couldn't check the voltage as I don't have a filtering voltmeter.

                                            As you see, all supplied values differ from the info sheet. Clearly the thoughtful manufacturers have provided a generic info sheet and couldn't be a***d to amend it for different products.

                                            When I did the unit reset, all values returned (approximately) to those on the info sheet, but the AT4 was definitely not working as it should. Normal function was only restored when I re-entered the 'as supplied' parameter values as above.

                                            On set up, I only checked to see if there was a voltage from the PE terminal ( you can actually just see it marked in your photo) to the mains earth and there was no potential, but then I wasn't expecting any – maybe I should check again because all may not be well if there is a voltage present.

                                            I didn't ever record the voltage across the VR as it didn't seem to be an issue at the time. Unfortunately, my unit is not on the bench at the moment pending works to the drill for which it was purchased for. I will see If I can cobble something up tonight and let you know.

                                            #474489
                                            Martin of Wick
                                            Participant
                                              @martinofwick

                                              Just to avoid tail chasing,

                                              we are sure that it is a new and/or tested 10k Pot and that P10 is set at 2 with P11 set at 2?

                                              Edited By Martin of Wick on 24/05/2020 14:02:38

                                              #474500
                                              Andrew Firman
                                              Participant
                                                @andrewfirman12129

                                                Many thanks Martin,

                                                The PE terminal is quite easy to see when the board is removed from the case. There is a red wire that connects the terminal and the main board and then through the brass board supports to the fins

                                                3fcf7c55-251c-42e1-8f83-90d130e3ac72.jpeg

                                                4774e486-a37c-4d6c-9941-1e50b017f6e5.jpeg

                                                The pot is new with a measured resistance of 10.7K . It seems ok but I don’t have any others to swap it with – awaiting a couple from China. I have set P10 and P11 to 2.

                                                I’ve checked the voltage between fins and a mains supply earth connected to the PE terminal and now get a reading of 3v ac down from 85v. Don’t know why it’s not zero but I guess one can live with 3v

                                                I’ve gone through all the “as supplied” parameters (including those not listed on the manual) on one vdf and once I’ve done it for the second one I’ll post a list listing all parameter settings “as supplied” .

                                                #474503
                                                Andrew Firman
                                                Participant
                                                  @andrewfirman12129

                                                  The pot I’m using.

                                                  4c2612ff-9b4b-4387-9919-f16df5aa632d.jpeg

                                                  #474645
                                                  Andrew Firman
                                                  Participant
                                                    @andrewfirman12129
                                                    Posted by James Walker on 23/05/2020 21:58:39:

                                                    Gents I have 2 of these VFDs commissioned on a Dah Lih mill. They run the Vertical, Horizontal and Power Feed motors. All motors are 380/400V 3ph. They are wired up to expect that range.

                                                    As noted this model VFD converts 220-240V 1PH in and spits out 380V/3PH.

                                                    The control pot I use is 10K. It is wired per the manuals instructions. I used Parameters P73 and P74 as noted by Bruce to adjust to get the response I wanted from the 10K pot.

                                                    I am happy to check and post the parameters I have set for all the key values if that is of interest and would be helpful.

                                                    I know when I did my install the level of info on this control as a bit like getting blood from a stone. So after lots of experimenting I solved most things and have it operating.

                                                    Cheers,

                                                    James.

                                                    Sorry James, I somehow missed your post. I would be very grateful if you would post your parameter settings.

                                                    As you say blood from a stone…. and to add insult to injury one of the 2 AT4s I have no longer powers my test motor smoothly, so another issue to sort…,.

                                                    #474727
                                                    SillyOldDuffer
                                                    Moderator
                                                      @sillyoldduffer

                                                      Don't get hung up on the value of the potentiometer!

                                                      It's used to divide a voltage, and, provided it doesn't draw too much current, almost any value will do.

                                                      The AT series 5V/10V output is specified to deliver up to 20mA. When a 10kΩ pot is used it draws 1mA. A 4.7kΩ pot draws 2.1mA The difference is trivial.

                                                      There are limits: the speed control input needs a certain amount of current to work, and a high-value pot might not provide enough. And a very low-value pot will draw too much current, possibly damaging itself or the power supply.

                                                      For this application I'd guess any pot between 1kΩ and 100kΩ will work, with 3.3 to 10kΩ being typical.

                                                      Dave

                                                    Viewing 25 posts - 1 through 25 (of 74 total)
                                                    • Please log in to reply to this topic. Registering is free and easy using the links on the menu at the top of this page.

                                                    Advert

                                                    Latest Replies

                                                    Home Forums General Questions Topics

                                                    Viewing 25 topics - 1 through 25 (of 25 total)
                                                    Viewing 25 topics - 1 through 25 (of 25 total)

                                                    View full reply list.

                                                    Advert

                                                    Newsletter Sign-up