3 Phase Motor HP?

Advert

3 Phase Motor HP?

Home Forums Workshop Tools and Tooling 3 Phase Motor HP?

Viewing 25 posts - 1 through 25 (of 38 total)
  • Author
    Posts
  • #98142
    _Paul_
    Participant
      @_paul_

      I have a 3 phase motor looks like an older squirrel cage Brooks/Crompton sadly it's missing it's information plate.

      What is the most accurate method of calculating it's KW or HP?

      The motor is wired Delta and has an across the terminals resistance of 8.2 Ω dividing this by 1.5x gives a single winding resistance of 12.3 Ω.

      Using Ohms law my calculations have given me this:

      V/R = I. therefore 230v ÷ 12.3 Ω gives 18.6992 Amps (I)

      230v x 18.6992 Amps = 4.3 Kw ÷746 = 5.765 HP

      Looking at the size of the motor it dosen't seem big enough to be this powerful, but that said it won't run for long on my 2HP RPC before the switch trips out.

      Any & all help appreciated.

      Paul

      Advert
      #16881
      _Paul_
      Participant
        @_paul_
        #98155
        jason udall
        Participant
          @jasonudall57142

          you have measured the "DC" resistance of the COLD windings..

          I say cold since that value varies with temperature and rises as the motor heats up.

          Simpler way to power( watts or horse) would be ( 230*230/R) ( just algerbra)

          1) your calculated current would be closer to the stall current (0 rpm) of the motor ( again cold but would drop as the windings heat up ..eeek!)

          2 FLA is a term oftern used with motors ( full load amps ) this figure would be closer for that calculation of horse power..( and is rule of thumb about 1/10 of stall current)

          3 You say delta…so lets assume three phase … thus each "phase " is doing the (230 *230)/R thing so hp would be triple what you calculate… ( but see 1 and 2)

          so my guess would be (3*230*230/12.3 )/10(ish !) =1290 W or1.7 hp

          stall/fla guess ——–kW—— hp

          5————————- 2.5 ——3.4

          8 ———————— 1.6—— 2.2

          10 ———————- 1.3 —– 1.7

          12 ———————- 1.0 —– 1.4

           

          hope this helps and not just fogs the matter

           

          Indeed edited by Jason..to fix the formating decisions made for me by this PXXXXY editor 

          V
          V
          V

          Edited By jason udall on 11/09/2012 09:34:20

          #98158
          Les Jones 1
          Participant
            @lesjones1

            Hi Paul,
            There are a few errors in your reasoning. The resistance part of your calculation is correct. The current calculation is wrong as the voltage between phases is 398 (sqrt 3 x 230) Also you have only considered the power in one winding so you also need to multiply by 3 This is not the main flaw in your reasoning. Your reasoning treats each winding a a pure resistor. If this was true all the power would be converted to heat. You cannot work out the power consumed by a motor by just considering the winding resistance. I think you would be better off trying to find a cataloge of motors of a similar age and rotational speed and compare physical sizes. Do not compare it with modern motors which are smaller in size. These tend to run hotter as modern insulation can withstand higher temperatures.

            Les.

            #98169
            KWIL
            Participant
              @kwil

              There is a little thing called inductance that is missing from all of this, we are dealing with AC. What diameter is the main casing and the shaft diameter?

              #98173
              jason udall
              Participant
                @jasonudall57142

                Indeed Kwil.. inductance and back emf and various others.. but the OP started simply and a rule of thumb type approach appeared usefull.

                A motor is not even a pure inductor , motors are more complex and theres phase angle to include in the V.I product.( vector vs scalar arithmatic ) I know or at least have forgotten much of my AC theory.

                But ..but the OP has made some sensible tests.. might suggest test motor off load measure I and work from there…

                #98189
                Russell Eberhardt
                Participant
                  @russelleberhardt48058

                  The only real way to measure the power is to power it up and load it with a brake until the speed drops to its rated speed, usually 1440 rpm., then measure the output power. Dificult unless you have or can improvise a dynamometer. Instead you could measure the electrical power input which will be perhaps 10% higher. Again that's difficult without a power meter, amps times volts doesn't work.

                  I really think your best approach is to see if it will do the job. If it runs slow or overheats it's not powerful enough.

                  Russell

                  #98195
                  Steve Garnett
                  Participant
                    @stevegarnett62550

                    KWIL is asking the sensible questions, I think – give us some physical dimensions and we can make a much better guess at what the rating plate might have said… I have 2 or 3 different Brookes/Comptons to check against, and I'm sure that others do as well.

                    #98210
                    Sub Mandrel
                    Participant
                      @submandrel

                      DC resistance will only tell you the approximate stall current of the motor, which will, in practice, still be a bit less due to inductive effects on AC.

                      It is, indeed, the physical size of the motor which is the best guide to its power as this limits how much heat it can dissipate. Also, the diameter of the copper wire in the windings should give a clue as to the maximum working current.

                      Follow some of these links: **LINK**

                      Neil

                      #98216
                      _Paul_
                      Participant
                        @_paul_

                        Thank you gentlemen some very good food for thought.

                        Some more information:

                        Dimensions:

                        Length bell to bell 10"

                        Diameter 6-3/8"

                        Shaft Diameter 5/8"

                        Running (unloaded) RPM 2970 (difficult to load up as it's a T&C grinder)

                        Voltages:

                        L1 – L2 = 250v

                        L2 – L3 = 230v

                        L1 – L3 = 240v

                        Voltage mismatch is down to the homebrew 2HP RPC it is running from.

                        Amperages:

                        L1 = 1.5

                        L2 = 1.1

                        L3 = 0.7

                        Above measurements taken with motor running @ 28 degrees C

                        And as they say a picture paints a thousand words….

                        Thats a 6" wheel in the pics.

                        Paul

                        #98220
                        Nathan Sharpe
                        Participant
                          @nathansharpe19746

                          Quick and dirty way of working it out from the under ower figures posted:

                          Multiply highest voltage by highest amperage = approx watts that winding, mutiply that by 3, multiply that by 0,8 .That should be accurate enough for most purposes. I figure it at about 1.1 to 1.3 Kw.

                          Nathan.

                          #98222
                          Nathan Sharpe
                          Participant
                            @nathansharpe19746

                            You could of course ignore my previous post and look at the obvious, it,s running on your 2hp(1100w) converter !! Why didn,t I do that?

                            Nathan.

                            #98242
                            Steve Garnett
                            Participant
                              @stevegarnett62550

                              Hmm… not quite sure how you arrived at that exactly…

                              Generally, we assume that 1hp is about 750W. And with that frame size, and it being a 2-pole motor (we can tell that from the unloaded speed), Brooke Compton typically made 1 and 1.5hp motors. The 2hp ones are a little bit larger – much easier to keep them cool. And they have a larger diameter shaft, as well.

                              But from the numbers given, I'd say that by the simple expedient of multiplying the average voltage by the total current (which is the correct product!), you get a power consumtion of 792W – which, taken along with the frame dimensions, pretty firmly makes it a 1hp motor, I'd say.

                              Edited By Steve Garnett on 12/09/2012 10:46:57

                              #98264
                              Russell Eberhardt
                              Participant
                                @russelleberhardt48058

                                If it's running at 2970 rpm it is very lightly loaded indeed. Nominal no load speed will be 3000 rpm and fully loaded speed is 2880 rpm. For small degrees of slip ( the speed drop) slip is proportional to load power. Thus if you are taking about 1 hp at the moment you can take nearly 4 hp from it before the speed drops below 2880 rpm (provide of course that it doesn't overheat which would be unlikely for ittermittent loading). More than adequate for your grinder I should think!

                                Russell

                                #98270
                                Steve Garnett
                                Participant
                                  @stevegarnett62550
                                  Posted by Russell Eberhardt on 12/09/2012 21:20:34:

                                  Thus if you are taking about 1 hp at the moment you can take nearly 4 hp from it before the speed drops below 2880 rpm (provide of course that it doesn't overheat which would be unlikely for ittermittent loading).

                                  Not from an old Brookes Crompton he won't… These are pretty lossy, and will lose power rapidly. You can get a much more sensible drive for them from a modern inverter, and with care compensate for the torque/speed characteristics somewhat. I still remember the first time I did this – something of a revelation!

                                  #98300
                                  _Paul_
                                  Participant
                                    @_paul_

                                    Gentlemen again thank you for some very positive advice.

                                    It seems I have by popular consensus a 1HP (or thereabouts) motor.

                                    I can appreciate the difficulties of having a mixed bag of parameters to work from with differing motor types/sizes but is there no definitive equation?, how do the motor repair workshops establish a "rogue" motors HP or do they use some kind of Dyno?

                                    Regards

                                    Paul

                                    #98324
                                    Russell Eberhardt
                                    Participant
                                      @russelleberhardt48058
                                      Posted by Steve Garnett on 12/09/2012 23:34:03:Not from an old Brookes Crompton he won't… These are pretty lossy, and will lose power rapidly. You can get a much more sensible drive for them from a modern inverter, and with care compensate for the torque/speed characteristics somewhat. I still remember the first time I did this – something of a revelation!

                                      Both the torque and the current are directly proportional to the slip up to normal working levels. Motors under 5 hp or so are designed for a slip rating of about 4% at their designed output power. Bigger motors have a lower slip rating. Without slip there is no torque developed. As I said you can load the motor until it's speed drops to about 2880 rpm and get the rated power output.

                                      I do however suspect that his input power measurement is a little off. The bottom line however is that he is currently running at a slip of only 1% so is running at about 1/4 rated power. The motor is more than adequate for the use it is put to.

                                      I must agree with you that an electronic inverter drive is the way to go. My lathe and mill are both fitted with them.

                                      Russell.

                                      #98344
                                      Steve Garnett
                                      Participant
                                        @stevegarnett62550
                                        Posted by Russell Eberhardt on 13/09/2012 17:17:56:

                                        Both the torque and the current are directly proportional to the slip up to normal working levels. Motors under 5 hp or so are designed for a slip rating of about 4% at their designed output power. Bigger motors have a lower slip rating. Without slip there is no torque developed. As I said you can load the motor until it's speed drops to about 2880 rpm and get the rated power output.

                                        I do however suspect that his input power measurement is a little off. The bottom line however is that he is currently running at a slip of only 1% so is running at about 1/4 rated power. The motor is more than adequate for the use it is put to.

                                        You've also assumed that the rpm measured is accurate – generally it's easier to measure current accurately than speed (unless you are specifically set up to do this). And if you go back to the original post, you'll see that this motor, with its low loading, already won't run for long without tripping out the rpc that's driving it – supposedly rated at 2hp.

                                        So whilst I also suspect the current consumption, it's for a slightly different reason; there's something altogether not right about it. We know that those motors are rated, at that size, at 1.5hp max, and this one's drawing, to a first approximation, the sort of current that it should be when loaded and running at its rated speed for a 1hp. And running at 28 degrees with that light a load? Seems to be a tad warm to me, especially as this is likely to be a case reading – how warm is it inside? I think I'd be wanting to have a careful look at this before relying on it.

                                        Edited By Steve Garnett on 13/09/2012 21:17:38

                                        #98361
                                        Nathan Sharpe
                                        Participant
                                          @nathansharpe19746

                                          As an edit to my 2nd post I,ll change the wattage figure for the converter from 1100W to 1500W, apologies.

                                          The very quick calc is one I was given by an instructor at Maddon generators more years ago than I care to remember and is the one I,ve used at work to calculate the generated output required to start a motor of any size (3PH) from a mobile/portable Genset— works for me— for the previous 35 years. Just use Ohms law to apply it to motor Wattage.

                                          I do agree that the L1 figure is "iffy" but is probably correct given that the inverter is driving L2/L3 through capacitors. Small changes of capacitor values serving L2/L3 would give more balance to the circuit.

                                          Doing the calc L1+L2+L3 in running Watts= 776 W, so given the motor/winding temp 1100/1300 W is somewhere very close.

                                          The motor/winding temp will fall with better phase balance.

                                          Do the calc, Total V(L1+L2+L3) divided by Total A (L1+L2+L3) This also puts you somewhere close.

                                          There will always be variation due to temp and stopping/starting a motor during testing will always make it worse as the motor does not dissipate start up heat until it,s been run for a while.

                                           

                                          Nathan.

                                           

                                          Edited By Nathan Sharpe on 13/09/2012 23:39:34

                                          #98382
                                          Russell Eberhardt
                                          Participant
                                            @russelleberhardt48058

                                            Posted by Steve Garnett on 13/09/2012 21:15:50:

                                            You've also assumed that the rpm measured is accurate – generally it's easier to measure current accurately than speed (unless you are specifically set up to do this).

                                            Agreed. With the measured 1% slip an error of 0.5% in the measured speed would give a 50% error in the torque or power calculations!

                                            With an ordinary multimeter the current measurement is likely to be within about 5% but the input power is not given by I x V. Power factor must be taken into account, which is likely to be quite low at such low loading.

                                            I think the only valid conclusion from all the above posts is that the motor is adequate for the job but there is a problem with the converter.

                                            Russell.

                                            #98396
                                            Steve Garnett
                                            Participant
                                              @stevegarnett62550

                                              FWIW, I looked up what Brook Crompton have to say about iron-frame motors and their overall performance, which entirely confirms what I suspect. They give a perfectly reasonable forumula which says:

                                              output hp= (V * A * Efficiency * Power Factor * 1.732)/746

                                              If we assume that the efficiency and power factor figures are in the normal range for an unloaded three-phase motor, then the product of these * 1.732 is going to be approaching unity (I've guessed a value of around 0.9), then the end figures look like:

                                              (240 * 3.3 * 0.9)/746 = 0.955hp.

                                              That's as near to 1 as makes no odds. All the stuff about temperature will make a difference to the efficiency figure, certainly – but not a huge amount of difference to the end result.

                                              It is a 1hp motor!

                                              #98422
                                              Russell Eberhardt
                                              Participant
                                                @russelleberhardt48058

                                                Steve,

                                                That formula is correct but the efficiency of an unloaded motor must, by definition be zero as it provides no output power.

                                                His motor is loaded but only very lightly so the efficiency will be much lower than 0.9. What exactly it is we cannot know.

                                                Russell.

                                                #98455
                                                _Paul_
                                                Participant
                                                  @_paul_

                                                  Gentlemen, thank you very much for the inclusive edification.

                                                  My homebrew RPC had some issues so after rewiring it and making quite a few replace & test (poke & hope) capacitance changes I now get the following:

                                                  The grinder running (unloaded) at a consistent 2970 RPM (RPM measured using a Chinese LED/Laser counter)

                                                  Voltages:

                                                  L1 – L2 = 239v

                                                  L2 – L3 = 239v

                                                  L1 – L3 = 230v

                                                  Voltage mismatch is down to what I think is an acceptable difference but once I have some alternate sizes of capacitors delivered I will try to tune if further.

                                                  Amperages:

                                                  L1 = 1.1

                                                  L2 = 1.1

                                                  L3 = 0.9

                                                  As a test I also ran my Boxford Lathe(3/4hp Gryphon) off the same RPC at the same time this gave little variation in voltage but the amperage readings then developed into this:

                                                  L1 = 1.9

                                                  L2 = 1.9

                                                  L3 = 2.4

                                                  The changes to the RPC have made the grinder motor very smooth with no trip outs, bizarrely the Boxford motor now runs smoother on the RPC than when it is running from my Teco inverter.

                                                  Steve, the formula from Brook Crompton was exactly what I was looking for many thanks.

                                                  Regards

                                                  Paul

                                                  #98471
                                                  Russell Eberhardt
                                                  Participant
                                                    @russelleberhardt48058

                                                    Glad to hear you have it sorted.

                                                    Russell.

                                                    #98474
                                                    _Paul_
                                                    Participant
                                                      @_paul_

                                                      Russel my thanks to you also, your prognosis about the RPC being "off" was quite correct.

                                                      It;s still not 100% but a hopefully a bit more capacitor tuning will get it better, what I have noticed though is as more motors are added the values dont climb exponentially as you might expect I am putting this down to the different types/styles of motor.

                                                      I am beginning to wonder if it may also be a factor that all the motors currently tested are not "natively" 230v and have been converted from Star (415v) only to Delta (230v) by me converting (picking out the star point in) each device.

                                                      I now find myself with more questions than answers.

                                                      Regards

                                                      Paul

                                                    Viewing 25 posts - 1 through 25 (of 38 total)
                                                    • Please log in to reply to this topic. Registering is free and easy using the links on the menu at the top of this page.

                                                    Advert

                                                    Latest Replies

                                                    Viewing 25 topics - 1 through 25 (of 25 total)
                                                    Viewing 25 topics - 1 through 25 (of 25 total)

                                                    View full reply list.

                                                    Advert

                                                    Newsletter Sign-up